Vacuum Heat Treatment Furnace
Vacuum Sintering Furnace
Vacuum Brazing Furnace
(The article comes from the Internet. If reprinting is not allowed, please contact our company to delete it.)
Please send us your inquiry about the customization of other furnace types or related questions about vacuum furnace. We will reply you immediately. Thank you.
Downloads
All documents in the overview
News & Press
All news at a glance
Request
Send us a message
Email: contact@vacfurnace.com
Tel : +86-21-50878190
Wechat : 2210154395
Address: NO.1299, XinJinQiao Road, Pudong New Area, Shanghai, China.
Copyright © 2010-2021 Shanghai Gehang Vacuum Technology Co.,Ltd. All Rights Reserved.
Vacuum annealing furnace working steps
Vacuum annealing furnace work steps are as follows:
1. send water first, check the water is smooth, water pressure р> 0.lMPa, or not allowed to open the furnace.
In the case of
2. Turn on the mains and close the power supply.
In the case of
3. Open the mechanical pump, respectively, open No. 1, No. 2 gate.
In the case of
4. Close the total power of the vacuum gauge, turn on the thermocouple power, adjust the heating current (current adjusted to 128A) to measure the vacuum.
In the case of
Current is 22mA when the vacuum is 10-1Torr (13.3Pa);
In the case of
Current is 84mA when the vacuum is 10-2Torr (1.33Pa);
In the case of
Current is 98mA when the vacuum is 10-3Torr (0.133Pa);
In the case of
When the current is 10OmA, the degree of vacuum is 10-4Torr (0.0133Pa).
In the case of
5. After the vacuum is higher than 1.33Pa, open the No. 3 vacuum valve, so that the vacuum inside the diffuser also reached 1.33Pa or more.
In the case of
6. Diffusion pump heating, about 40min later, the pump oil heating evaporation, then closed the No. 2 vacuum valve, and then open the high vacuum valve.
In the case of
7. Vacuum higher than 0.133Pa after the closure of “thermocouple power”, open the “ionization meter power”, with the ionization meter to measure the degree of vacuum.
In the case of
8. Adjust the electronic potential difference gauge needle to the required temperature value, adjust the “PID” to the specified proportional band and integral, the differential time (the proportion of 40% to 150%, the integration time is 6 ~ 2.5min, Differential time is 5 ~ 4min)
In the case of
9. Turn the circuit power “Manual” knob to the minimum, the switch to the “automatic” position, the “PID” regulator “manual” to the minimum, the switch hit the “manual” position, and connected to “PID “power supply.
In the case of
10. Electric furnace power supply, adjust the “PID” of the “manual”, so that the three-phase ammeter output indicates a basic balance in the 30 ~ 70A.
In the case of
11. When the furnace temperature is close to the reference value, set the “PID” furnace temperature control from “manual” to “automatic” for automatic control.
In the case of
12. After the insulation time to meet the requirements, such as the process requirements with the furnace cooling, can be closed electric furnace power supply. Such as the process requirements to control the cooling, that is, “PID” from the “automatic” hit “manual”, by “manual” to adjust the cooling.
In the case of
13.350 ℃ above are not allowed to close the water and vacuum system, closed diffusion pump, you must first close the high vacuum valve, and then close the No. 3 vacuum valve, open the No. 2 vacuum valve.
In the case of
14. When closing the mechanical pump, first close the No. 2 vacuum valve, and then closed the power supply.
In the case of
15. When the furnace temperature is higher than 150 ℃, are not allowed to deflate and open the lid.
In the case of
16. Work process must strictly abide by the above-mentioned safety technology manipulation procedures, are not allowed to leave the post, often pay attention to check the water, equipment, vacuum, motor, transformer, fan, meter and other operations are normal, abnormal, timely report processing.